OBC 2006 › Division B
3.7.4.9.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.7.4.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.7.4.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
Provenance
OBC 1997 · continues from 3.7.4.9. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 137/07, cl. 22 · ext v1 →
In force 2007-04-02
Next: O. Reg. 137/07, cl. 22 · ext (not in force until 2007-04-02) v1 →
OBC 2012 · continues as 3.7.4.9. — Pro
3.7.4.9. — Plumbing Fixtures for Industrial Occupancies
(1) Except as provided in Sentence (2), the number of water closets and lavatories required for industrial occupancies shall conform to Table 3.7.4.9.
(2) Not more than one water closet to serve both sexes need be provided in a Group F occupancy where,
(a) the occupant load is not more than 9 persons, or
(b) the total area of the occupancy, excluding basements, is not more than 300 m2.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Number of Persons of Each Sex | Minimum Number of Water Closets and Lavatories for Each Sex |
up to 9 | 1 |
10 to 24 | 2 |
25 to 49 | 3 |
50 to 74 | 4 |
75 to 100 | 5 |
over 100 | 6 plus 1 for each additional increment of 30 persons of each sex in excess of 100 |