3.6.2.8. — Emergency Power Installations

(1) A generator to supply emergency power for lighting, fire safety and life safety systems shall be located in a room that,

(a) is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than ,

(i) 2 h for buildings within the scope of Subsection 3.2.6.v1, and

(ii) 1h for other buildings, and

(b) contains only the generating set and equipment that is related to the emergency power supply system.