OBC 2006 › Division B
3.2.7.9.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.7.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
(5) Sections 23, 26 and 31, subsection 32 (2), sections 36, 40, 45, 46 and 48 and subsection 214 (2) come into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(5)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.7.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
(5) Sections 23, 26 and 31, subsection 32 (2), sections 36, 40, 45, 46 and 48 and subsection 214 (2) come into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(5)
Provenance
OBC 1997 · continues from 3.2.7.9. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 31 · ext v1 →
In force 2010-04-01
Next: O. Reg. 503/09, cl. 31 · ext (not in force until 2010-04-01) v1 →
OBC 2012 · continues as 3.2.7.9. — Pro
3.2.7.9. — Emergency Power for Building Services
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · viewing · 2006-12-31(1) An emergency power supply capable of operating under a full load for not less than 2 h shall be provided by an emergency generator for,
(a) every elevator serving storeys above the first storey in a building that is more than 36 m high measured between grade and the floor level of the top storey and every elevator for fire fighters in conformance with Sentence (2),
(b) water supply for fire fighting in conformance with Article 3.2.5.7., if the supply is dependent on electrical power supplied to the building, and the building is within the scope of Subsection 3.2.6.,
(c) fans and other electrical equipment that are installed to maintain the air quality specified in Article 3.2.6.2., and
(d) fans required for venting by Article 3.2.6.10.
(2) Except as permitted by Sentence (3), the emergency power supply for elevators required by Clause (1)(a) shall be capable of operating all elevators for fire fighters plus one additional elevator simultaneously.
(3) Sentence (2) does not apply if the time to recall all elevators under emergency power supply is not more than 5 min, each from its most remote storey to,
(a) the storey containing the entrance for fire fighter access referred to in Articles 3.2.5.4 and 3.2.5.5., or
(b) to a transfer lobby.
(4) Except as provided by Sentence (5), an emergency power supply capable of operating under a full load for not less than 30 min shall be provided by emergency generator for water supply for fire fighting in conformance with Article 3.2.5.7., if the supply is dependent on electrical power supplied to the building, and the building is not within the scope of Subsection 3.2.6.
(5) Sentence (4) does not apply to the water supply for a standpipe system.
v1 O. Reg. 503/09
Later · 2010-04-01(1) An emergency power supply capable of operating under a full load for not less than 2 h shall be provided by an emergency generator for,
(a) every elevator serving storeys above the first storey in a building that is more than 36 m high measured between grade and the floor level of the top storey and every elevator for fire fighters in conformance with Sentence (2),
(b) water supply for fire fighting in conformance with Article 3.2.5.7., if the supply is dependent on electrical power supplied to the building, and the building is within the scope of Subsection 3.2.6.,
(c) fans and other electrical equipment that are installed to maintain the air quality specified in Article 3.2.6.2., and
(d) fans required for venting by Article 3.2.6.6.
(2) Except as permitted by Sentence (3), the emergency power supply for elevators required by Clause (1)(a) shall be capable of operating all elevators for fire fighters plus one additional elevator simultaneously.
(3) Sentence (2) does not apply if the time to recall all elevators under emergency power supply is not more than 5 min, each from its most remote storey to,
(a) the storey containing the entrance for fire fighter access referred to in Articles 3.2.5.4 and 3.2.5.5., or
(b) to a transfer lobby.
(4) Except as provided by Sentence (5), an emergency power supply capable of operating under a full load for not less than 30 min shall be provided by emergency generator for water supply for fire fighting in conformance with Article 3.2.5.7., if the supply is dependent on electrical power supplied to the building, and the building is not within the scope of Subsection 3.2.6.
(5) Sentence (4) does not apply to the water supply for a standpipe system.