OBC 2006 Division B

3.2.6.1.

Version 1 — in force 1 April 2010

In force · amended
Verified · covered Verified against the 2010-04-01–2010-06-30 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.2.6.1. — Pro

Base · O. Reg. 350/06 · ext v0 →

O. Reg. 205/08, cl. 7 · ext ← current

In force 2010-04-01

OBC 2012 · continues as 3.2.6.1. — Pro

3.2.6.1. — Application

(1) This Subsection applies to a building,

(a) of Group A, D, E or F major occupancy classification that is more than,

(i) 36 m high, measured between grade and the floor level of the top storey, or

(ii) 18 m high, measured between grade and the floor level of the top storey, and in which the cumulative or total occupant load on or above any storey above grade, other than the first storey, divided by 1.8 times the width in metres of all exit stairs at that storey, exceeds 300,

(b) containing a Group B major occupancy in which the floor level of the highest storey of that major occupancy is more than 18 m above grade,

(c) containing a floor area or part of a floor area located above the third storey designed or intended as a Group B, Division 2 or 3 occupancy, and

(d) containing a Group C major occupancy whose floor level is more than 18 m above grade.