OBC 2006 Division B

3.2.4.12.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.2.4.12. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · renumbered to 3.2.4.13. — Pro

3.2.4.12. — Prevention of Smoke Circulation

(1) If a fire alarm system is installed, an air handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector if the air handling system,

(a) serves more than one storey,

(b) serves more than one suite in a storey,

(c) serves more than one fire compartment required by Sentence 3.3.3.5.(2)v1 or

(d) is not provided with fire-dampers as permitted by Sentence 3.1.8.8.(8)

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 3.2.4.12. of Division B, which lists the conditions in Sentence (1) without a comma before 'or (d)' and ends the sentence without a closing period. As of its September 24, 2009 re-render the e-Laws consolidation editorially inserts a comma before 'or (d)' and adds a closing period, with no amending regulation making the change — O. Reg. 365/09 (effective September 24, 2009) does not amend this Article. This map preserves the as-filed punctuation.

Text · e-Laws consolidated snapshot