CodeChronicle

OBC 2006 Division B

3.2.2.74.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.2.2.74. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 3.2.2.74. — Pro

3.2.2.74. — Group F, Division 3, up to 6 Storeys

(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided,

(a) it is not more than 6 storeys in building height, and

(b) it has a building area not more than the value in Table 3.2.2.74.

(2) The building referred to in Sentence (1) shall be of noncombustible construction, and,

(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,

(b) mezzanines shall have a fire-resistance rating not less than 1 h,

(c) roof assemblies shall have a fire-resistance rating not less than 1 h, and

(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.

Text · e-Laws consolidated snapshot

Table 3.2.2.74. Maximum Building Area, Group F, Division 3, up to 6 Storeys Forming Part of Sentence 3.2.2.74.(1)

Column 1

Column 2

Column 3

Column 4

No. of Storeys

Maximum Area, m2

Facing 1 Street

Facing 2 Streets

Facing 3 Streets

1

not limited

not limited

not limited

2

7 200

9 000

10 800

3

4 800

6 000

7 200

4

3 600

4 500

5 400

5

2 880

3 600

4 320

6

2 400

3 000

3 600