3.2.2.69. — Group F, Division 2, up to 4 Storeys, Increased Area

(1) A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided,

(a) it is not more than 4 storeys in building height, and

(b) it has a building area not more than the value in Table 3.2.2.69.A. or Table 3.2.2.69.B.

(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,

(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,

(b) mezzanines shall have a fire-resistance rating not less than 1 h,

(c) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and

(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.

Text · e-Laws consolidated snapshot

Table 3.2.2.69.A. Maximum Building Area, Group F, Division 2, up to 4 Storeys, Increased Area Forming Part of Sentence 3.2.2.69.(1)

Column 1

Column 2

Column 3

Column 4

No. of Storeys

Maximum Area, m2

Facing 1 Street

Facing 2 Streets

Facing 3 Streets

1

6 000

7 500

9 000

2

3 000

3 750

4 500

3

2 000

2 500

3 000

4

1 500

1 875

2 250

Table 3.2.2.69.B. Maximum Building Area, Group F, Division 2, up to 4 Storeys, Increased Area, Sprinklered Forming Part of Sentence 3.2.2.69.(1)

Column 1

Column 2

No. of Storeys

Maximum Area, m2

1

18 000

2

9 000

3

6 000

4

4 500