3.2.2.55.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.2.2.55. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 3.2.2.55. — Pro

3.2.2.55. — Group D, up to 2 Storeys

(1) A building classified as Group D is permitted to conform to Sentence (2) provided,

(a) it is not more than 2 storeys in building height, and

(b) it has a building area not more than the value in Table 3.2.2.55.

(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,

(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min, and

(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,

(i) have a fire-resistance rating not less than 45 min, or

(ii) be of noncombustible construction.

Text · e-Laws consolidated snapshot

Table 3.2.2.55. Maximum Building Area, Group D, up to 2 Storeys Forming Part of Sentence 3.2.2.55.(1)

Column 1

Column 2

Column 3

Column 4

No. of Storeys

Maximum Area, m2

Facing 1 Street

Facing 2 Streets

Facing 3 Streets

1

1 000

1 250

1 500

2

800

1 000)

1 200