3.2.2.19.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.2.2.19. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 3.2.2.19. — Pro

3.2.2.19. — Buildings Containing Impeded Egress Zones

(1) A building containing an impeded egress zone and conforming to the appropriate requirements of Articles 3.2.2.20. to 3.2.2.83. is not required to conform to the requirements of Articles 3.2.2.36. and 3.2.2.37. for a Group B, Division 1 major occupancy provided,

(a) the building is sprinklered,

(b) it is not more than 1 storey in building height,

(c) it does not include,

(i) a contained use area,

(ii) sleeping accommodation,

(iii) a high hazard industrial occupancy, or

(iv) a mercantile occupancy,

(d) the building area is not more than 6 400 m2 if the building includes a medium hazard industrial occupancy,

(e) the impeded egress zone does not extend beyond the boundaries of the fire compartment in which it is located, and

(f) the occupant load of the impeded egress zone is not more than 100.