3.1.9.5. — Openings through a Membrane Ceiling

(1) A membrane ceiling forming part of an assembly assigned a fire-resistance rating on the basis of Supplementary Standard SB-2 is permitted to be penetrated by openings leading into ducts within the ceiling space provided,

(a) the ducts are sheet steel, and

(b) the amount of openings and their protection conform to the requirements of Supplementary Standard SB-2.

(2) Fire stop flaps in ceiling membranes required in Sentence (1) shall conform to CAN4-S112.2-M, “Fire Test of Ceiling Firestop Flap Assemblies”.