3.1.8.18. — Sprinkler Protected Glazed Wall Assembly

(1) A sprinkler protected glazed wall assembly shall be constructed in accordance with the requirements of ULC/ORD C263.1, “Sprinkler-Protected Windows Systems”.

(2) A sprinkler protected glazed wall assembly shall not be installed in,

(a) fire separations requiring a fire resistance rating of more than 2 hours,

(b) a firewall,

(c) a high hazard industrial occupancy, or

(d) any part of an exit serving,

(i) a floor area subject to the requirements of Subsection 3.2.6.v1,

(ii) a care and detention occupancy, or

(iii) a residential occupancy.

(3) Where a sprinkler protected glazed wall assembly is installed in an exit fire separation permitted in Sentence (2),

(a) the building shall be sprinklered, and

(b) the exits protected with the sprinkler protected glazed wall assemblies shall not comprise more than one half of the required number of exits from any floor area.