3.1.13.2. — Flame-Spread Rating

(1) Except as otherwise required or permitted by this Subsection, the flame-spread rating of interior wall and ceiling finishes, including glazing and skylights, shall be not more than 150 and shall conform to Table 3.1.13.2.

(2) Except as permitted by Sentence (3), doors, other than those in Group A, Division 1 occupancies, need not conform to Sentence (1) provided they have a flame-spread rating not more than 200.

(3) Doors within a dwelling unit need not conform to Sentences (1) and (2).

(4) Up to 10% of the total wall area and 10% of the total ceiling area of a wall or ceiling finish that is required by Sentence (1) to have a flame-spread rating less than 150 is permitted to have a flame-spread rating not more than 150, except that up to 25% of the total wall area of lobbies described in Sentence 3.4.4.2.(2) is permitted to have a flame-spread rating not more than 150.

(5) Except in the case of Group A, Division 1 occupancies, combustible doors, skylights, glazing and light diffusers and lenses shall not be considered in the calculation of wall and ceiling areas described in Sentence (4).

Editor's note

The notes to Table 3.1.13.2. are reproduced here as filed in O. Reg. 350/06. The consolidated e-Laws text applies editorial formatting changes to these notes that were not enacted by any regulation; this map preserves the notes as filed. The differences are: the heading "Notes to Table 3.1.13.2.:" appears in bold as filed and is rendered in regular weight on e-Laws; a space follows each note number ((1) and (2)) as filed, which e-Laws omits; and the reference in note (1) reads "Articles 3.1.13.8. and 3.1.13.10" as filed, to which e-Laws adds a trailing period ("3.1.13.10.").

Text · e-Laws consolidated snapshot

Table 3.1.13.2. Flame-Spread Ratings Forming Part of Sentence 3.1.13.2.(1)

Column 1

Column 2

Column 3

Occupancy, Location or Element

Maximum Flame-Spread Rating for Walls and Ceilings

Sprinklered

Not Sprinklered

Group A, Division 1 occupancies, including doors, skylights, glazing and light diffusers and lenses

150

75

Group B occupancies

150

75 (2)

Exits(1)

25

25

Lobbies described in Sentence 3.4.4.2.(2)

25

25

Covered vehicular passageways, except for roof assemblies of heavy timber construction in such passageways

25

25

Vertical service spaces

25

25

Notes to Table 3.1.13.2.:

(1) See Articles 3.1.13.8. and 3.1.13.10

(2) Group B occupancies are required to be sprinklered. See Part 11 for renovations of existing non-sprinklered Group B occupancies.