CodeChronicle

OBC 2006 Division B

3.1.10.2.

Version 1 — in force 1 April 2010

In force · amended
Verified · covered Verified against the 2010-04-01–2010-06-30 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.1.10.2. — Pro

Base · O. Reg. 350/06 · ext v0 →

O. Reg. 205/08, cl. 2 · ext ← current

In force 2010-04-01

OBC 2012 · continues as 3.1.10.2. — Pro

3.1.10.2. — Rating of Firewalls

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · 2006-12-31

(1) A firewall that separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h, except that where the upper portion of a firewall separates floor areas containing other than Group E or Group F, Division 1 or 2 major occupancies, the fire-resistance rating of the upper portion of the firewall is permitted to be not less than 2 h.

(2) A firewall that separates a building or buildings with floor areas containing major occupancies other than Group E or Group F, Division 1 or 2 shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 2 h.

(3) Except as permitted by Sentence (4), the required fire-resistance rating of a firewall, except for closures, shall be provided by masonry or concrete.

(4) A firewall permitted to have a fire-resistance rating not more than 2 h need not be constructed of masonry or concrete provided,

(a) the assembly providing the fire-resistance rating is protected against damage that would compromise the integrity of the assembly,

(b) the design conforms to Article 4.1.5.18.,

(c) the level of performance of the firewall is not less than of masonry or concrete in the areas of

(i) performance during fire conditions,

(ii) mechanical damage during the normal use of the building, and

(iii) resistance to damage from moisture,

(d) the firewall separates buildings or buildings with floor areas that do not contain,

(i) a Group B, Division 1 major occupancy, or

(ii) a Group B, Division 2 major occupancy, and

(e) the firewall does not separate buildings regulated by the provisions of Subsection 3.2.6.

v1 O. Reg. 205/08

Later · viewing · 2010-04-01

(1) A firewall that separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h, except that where the upper portion of a firewall separates floor areas containing other than Group E or Group F, Division 1 or 2 major occupancies, the fire-resistance rating of the upper portion of the firewall is permitted to be not less than 2 h.

(2) A firewall that separates a building or buildings with floor areas containing major occupancies other than Group E or Group F, Division 1 or 2 shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 2 h.

(3) Except as permitted by Sentence (4), the required fire-resistance rating of a firewall, except for closures, shall be provided by masonry or concrete.

(4) A firewall permitted to have a fire-resistance rating not more than 2 h need not be constructed of masonry or concrete provided,

(a) the assembly providing the fire-resistance rating is protected against damage that would compromise the integrity of the assembly,

(b) the design conforms to Article 4.1.5.18.,

(c) the level of performance of the firewall is not less than of masonry or concrete in the areas of

(i) performance during fire conditions,

(ii) mechanical damage during the normal use of the building, and

(iii) resistance to damage from moisture,

(d) the firewall separates buildings or buildings with floor areas that do not contain,

(i) a Group B, Division 1 major occupancy, or

(ii) a Group B, Division 2 major occupancy, and

(e) the firewall separates a sprinklered building regulated by the provisions of Subsection 3.2.6 from another sprinklered building.