12.3.3.9.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · merged from 9.38.3.7. — Pro

OBC 1997 · merged from 9.38.3.8. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

Content moved to SB-12, not yet covered

12.3.3.9. — Foundation Wall Insulation

(1) Sentence (2) applies to construction for which a permit has been applied for before January 1, 2009.

(2) Foundation walls enclosing heated space shall be insulated from the underside of the subfloor to not less than 600 mm below the adjacent exterior ground level.

(3) Sentence (4) applies to construction for which a permit has been applied for after December 31, 2008.

(4) Foundation walls enclosing heated space shall be insulated from the underside of the subfloor to not more than 380 mm above the finished floor level of the basement.

(5) Insulation applied to the exterior of a slab-on-ground floor shall extend down at least 600 mm below the adjacent exterior ground level or shall extend down and outward from the floor or wall for a total distance of at least 600 mm measured from the adjacent finished ground level.